Structural Quality Assurance Checklist
Predesign
- Required deliverables submitted
Schematic Design
- Required deliverables submitted
- Correct Building Code used
- Correct loads (Live, Snow, Wind Seismic) used
- Floor framing system(s) appropriate for the structure
- Roof framing system appropriate for the structure
- Lateral force system appropriate for the structure
Design Development
- Required deliverables submitted
- NPS structural standards followed
- Correct Building Code used
- Construction materials consistent with building type identified in code analysis (Types I, II, III, IV, V)
- Occupancy Category correct (Table 1604.5)
- Snow Load correct (1608)
- Snow Load Importance Factor correct (ASCE 7-05 Table 7-4)
- Roof LL correct (1607.11)
- Floor LL's correct (Table 1607.1)
- Wind velocity correct (Fig 1609)
- Wind exposure correct (1609.4)
- Wind Load Importance Factor correct (ASCE 7-05 Table 6-1)
- Seismic Ss and Sl correct (Fig. 1615(1) et al)
- Seismic Load Importance Factor correct (ASCE 7-05 Table 11.5-1)
- Foundation design consistent w/Geotech Report
- Footing extends below frost depth
- Floor framing system(s) appropriate for the structure
- Roof framing system appropriate for the structure
- Lateral force system appropriate for the structure
- Larger members for larger spans
- Larger footings at more heavily loaded columns
- Structural dimensions match Architectural drawings
- Column orientation matches Architectural drawings
- Column grid lines match Architectural drawings
- Column and bearing wall locations match Architectural drawings
- Complete and continuous load path for gravity loads (1604.4)
- Complete and continuous load path for lateral loads (1604.4)
- Outline specs provided for all required sections
100% Draft Construction Documents or 100% Draft Design-Build Construction Documents
General
- Required deliverables submitted
- NPS Structural standards followed
- Correct Building Code used
- Construction materials consistent with building type identified in code analysis (Types I, II, III, IV, V)
- Floor framing system(s) appropriate for the structure
- Roof framing system appropriate for the structure
- Lateral force system appropriate for the structure
- Larger members for larger spans
- Larger footings at more heavily loaded columns
- Structural dimensions match Architectural drawings
- Column orientation matches Architectural drawings
- Column grid lines match Architectural drawings
- Column and bearing wall locations match Architectural drawings
- Complete and continuous load path for gravity loads (1604.4)
- Complete and continuous load path for lateral loads (1604.4)
- Support for mechanical and electrical equipment
Loads
- Ocupancy Category correct (Table 1604.5)
- Snow Load correct (1608)
- Snow Load Importance Factor correct (ASCE 7-05 Table 7-4)
- Roof LL correct (1607.11)
- Floor LL's correct (Table 1607.1)
- Floor LL reduction (1607.9)
- Wind velocity correct (Fig 1609)
- Wind exposure correct (1609.4)
- Wind Load Importance Factor correct (ASCE 7-05 Table 6-1)
- Internal Pressure Coefficient Gcpi (ASCE 7-05 Table 6-7)
- Seismic Ss and Sl correct (Fig. 1615(1) et al)
- Seismic Load Importance Factor correct (ASCE 7-05 Table 11.5-1)
- Seismic Site Class correct (ASCE 7-05 11.4.2)
- Seismic Design Category correct (ASCE 7-05 Tables 11.6-1, 11.6-2)
- Flood loads (1612)
- Special loading conditions (cranes, heavy equipment, etc. (addressed))
- Requirements for special inspection shown
Foundation
- Foundation design consistent with Geotechnical Report
- Footing extends below frost depth (1805.2.1)
- Minimum footing width (1805.4.1)
- Footing step elevations close
- Foundation wall step elevations close
- Hold down locations clearly shown
- Seismic requirements for pile foundations
Concrete
- Minimum concrete cover shown (ACI 318-05 7.7)
- Tie spacing and arrangement correct (ACI 318-05 7.10.5.2)
16db longitudinal bars
48db tie wire
least dimension of tie wire
- Development length correct (ACI 318-05 12.2)
- Reinforcing continuity for negative moment areas (ACI 318-05 12.10.5)
- Control joint spacing in slabs-on-grade (24t is approximate)
- Expansion joints – floors, walls, roofs
- Two mats of steel provided for walls 10" and thicker (ACI 318-05 14.3.4)
- Minimum compression member reinforcing 0.01Ag ≤ As ≤ 0.08Ag (ACI 318-05 10.9.1)
- Minimum foundation pedestal reinforcing 0.005Ag ≤ As (ACI 318-05 15.8.2.1)
- Minimum footing thickness 6" above bottom reinforcing on soil (ACI318-05 15.7)
- Minimum footing thickness 12" above bottom reinforcing on piles (ACI318-05 15.7)
- Retaining wall reinforcing shown in the correct locations
Masonry
- Masonry dimensions modular
- Control joint locations and spacing for masonry construction
- Bond beams shown correctly
- Seismic requirements (ACI 530-05 1.14)
Steel
- A992 for W and Wt shapes
- Adequate stiffeners provided
- Complicated/unusual connection detailed
- Reactions/loads provided for connections not detailed
- Base plates – 4 anchor bolts minimum
- Minimum fillet weld size shown (AISC 9th Table J2.4)
- Special loading conditions for steel bar joists shown
- Bar joist connections at columns
- Bar joist seat depth correct
- Bar joist bridging shown
- Bar joist bridging connection to wall or frame
- Weld pattern for steel decks shown
- Sidelap and endlap fastening
- Steel decking continuous over three spans
Wood
- Notches and holes (2308.8.2, 2308.9.10, 2308.9.11, 2308.10.4.2)
- Truss bottom chords braced for compression due to load reversals
- Truss profiles provided for prefab trusses
- Truss loading requirements shown
- Permanent bracing of prefab trusses shown
- Cross grain bending and tension avoided
- Nailing schedule provided (Table 2304.9.1)
- Diaphragm and shearwall nailing shown
- Top plate splice detail shown
- Roof diaphragm shear transfer to shearwalls shown
Specs
- Contracting Officer vs. Engineer
- All required specification sections provided
- Shoring and bracing of excavations
- Compaction testing frequency
- Appropriate cement type
- Water-cement ratio 0.45 max
- Testing frequency
- Mortar and grout specified correctly
- Wood treatment – no CCA
- Materials conform to structural standards
Calcs
- Deflection limits correct (Table 1604.3)
- Concrete and masonry wall anchorage > 200 plf (1604.8.2)
- Stress increases (1605.3.1.1)
- Partition live load included (1607.5)
- Folding partitions accounted for
- Load combinations used correctly (1605.3)
- Roof DL corrected for slope
- Unbalanced snow loading (ASCE 7-05 7.6)
- Snow drifting (ASCE 7-05 7.7)
- Minimum wind pressure 10 psf for MWFRS (ASCE 7-05 6.1.4.1)
- Minimum wind pressure 10 psf for components & cladding (ASCE 7-05 6.1.4.2)
- Enclosed vs. partially enclosed
- Wind uplift addressed
- R, Ω, and Cd correct (AASCE 7-05 Table 12.2-1)
- Retaining walls (no requirement for F.S. > 1.5 for sliding and overturning) (1610.1)
- Ponding on flat roofs (1611.2)
- Flexural strength reduction (ACI318-05 9.3.2)
- Moment magnification considered for concrete columns (ACI 318-05, 10.11, 10.12, 10.13)
- Crack control for reinforced concrete structures (ACI 318-05 10.6.4)
- "Rolling" forces considered for purlins
- Second order effects considered for steel frames
- Load duration factors applied correctly for timber design (NDS-2001 Table 2.3.2)
- Allowable stress adjustment factors (NDS) applied correctly (NDS-2001 Table 4.3.1)
Submit 100% Complete Construction Documents or 100% Complete Design-Build Construction Documents for Final Approval
- Required deliverables submitted
- All review comments from 100% Draft Review satisfactorily resolved